TY-DB15
Category:SPD for computer
DB Port Signal SPD D-Sub 15
Tel:+86-577-62605321
Email:andy.xu@tycotiu.com
PDF DownloadFeatures:
Comply with IEC61643-21 standard
Nominal operating voltage Un: 12V
Protection level:IP20
Insertion loss:≤0.3dB
Connectiion:DB15
Excellent performance, low residual voltage, good protective effect
Parameters:
Model
TY-DB15
Test standards
IEC 61643-21
Max. continuous operating voltage
Uc
15VDC
C2 Nominal discharge current (8/20μs)[line-SG]
In
5kA
Voltage protection level [line-SG]
Up
≤40V
Operating temperature range
Tu
-40℃-80℃
Connection input / output
D-Sub 15 plug/socket
Enclosure material
Aluminium alloy
Degree of protection
IP20
Nominal voltage
Un
12V
C2 Nominal discharge current (8/20μs)[SG-PG]
In
10kA
Voltage protection level [SG-PG]
Up
≤500V
Response time [line-SG]
tA
≤1ns
Response time [SG-PG]
tA
≤100ns
Pinning
line: 2/9,4/11, SG: 8, PG: 1
Bandwidth
10 Mbps
Insertion loss
≤0.3dB
Application:
Suitable for DB15 port signal line lightning protection
Effectively reducing hardware and software failures caused by pulse interference, especially for high precision equipment equipped with microcomputer.
Installation and Maintenance:
Installed in series between the protected equipment and the antenna channel.
The input end of the lightning protection device is connected with the signal line, and the output end is connected with the protected equipment, which can not be connected in reverse.
During installation, the lines at both ends must be laid separately and cannot be tied together to prevent secondary induction.
Connect the grounding cable of the SPD to the grounding bar of the lightning protection system. The grounding cable should be short, thick, and straight to shorten the lightning current path as much as possible.
After installation and wiring, check that the wiring is correct and firm, then switch on the power supply and put into use