TY-BNC-H

TY-BNC-H

Category:SPD for coaxial

BNC Connector Antenna Signal Lightning Protector

Tel:+86-577-62605321
Email:andy.xu@chtaike.com.cn
PDF Download

Features:

Comply with IEC61643-21 standard

Large capacity, multi-level protection

Characteristic impedance:50Ω

Protection level:IP20

Insertion loss:≤0.3dB

Connectiion:BNC

Parameters:

Model


TY-BNC-H

Test standards


IEC 61643-21

Max. continuous operating voltage

Uc

180VDC / 130V AC

Nominal current

IL

20A

C2 Nominal discharge current (8/20μs)[line-shield/PG]
In 10kA

Voltage protection level [line-shield/PG]

Up

≤800V

Response time [line-shield/PG] tA ≤100ns

Operating temperature range

Tu

-40℃-80℃

Connection input / output


BNC

Bandwidth
3 Gbps
Insertion loss
≤0.3dB
Impedience
50Ω

Enclosure material


Steel

Degree of protection


IP20

Application:

Mainly used for the protection of equipment along the video signal line, such as video surveillance equipment (camera, video monitor, optical terminal, display, cable TV, home TV, etc.)

Prevent the surge invading the equipment along the feeder and causing damage

Installation and Maintenance:

Install in series in front of the protected equipment (or system),install as close to the protected equipment (or system) as possible.

The input end of the lightning protection device is connected with the signal line, and the output end is connected with the protected equipment, which can not be connected in reverse.

The PE grounding wire of the surge protector must be connected with the grounding system reliably, and the connecting wire should be short, thick and straight.

The product does not need special maintenance, Install as close to the device end as possible; When the work system failure, can be removed the lightning protection device, if system restored to the state before the use of normal, it should be replaced lightning protection device.